Specifications
General data | |
---|---|
Humidity | Measuring mode: Non-condensing (< 95 % RH) |
Operating pressure (max.) | Atmospheric (700 … 1,300 hPa) |
Supply voltage | 24 V DC ± 20 % |
Current consumption | Typ. < 35 mA (max. 80 mA) |
Analog outputs for wN and TM | 2 x 0 … 10 V (RL ≥ 10 kΩ; CL ≤ 1 nF) |
Electrical connection | Non-detachable cable, pigtail, 4 x 0,25 mm2, length 2 m, PVC |
Maximum cable length | 15 m |
Type of protection | IP40 |
Protection class | III (SELV) |
Minimum immersion depth | 35 mm |
Dimensions | ø 12 mm, probe length 144 mm, extension tube 97 mm (extending length 85 mm) |
Weight | 50 g (probe) |
Delivery content | Probe, mounting clamp, 1 pc. extension tube, manual |
Technical data | |
Measuring quantity | Standard flow velocity wN based on standard conditions 1) Medium temperature TM |
Measured medium | Clean air or nitrogen |
Measuring range wN | 0 ... 2.5 / 10 / 20 m/s |
Lower detection limit wN | 0.2 m/s |
Measuring range TM | 0 … +60 °C |
Measuring accuracy | |
Flow wN | 0 ... 2.5 m/s: ±(4 % of measured value + 0.05 m/s)2) 0 ... 10 m/s: ±(4 % of measured value + 0.2 m/s)2) 0 ... 20 m/s: ±(4 % of measured value + 0.4 m/s)2) |
Response time (t90) wN | Approx. 10 s (jump of wN from 0 to 5 m/s) |
Temperature gradient wN | < 1,5 K/min at 5 m/s |
Temperature TM (wN > 2 m/s) | ±1 K (10 … 30 °C); ±2 K (remaining interval) |
Operating temperature | |
Sensor | -10 … +60 °C |
Material | |
Sensor | PC, ABS, Brass nickel plated, PVC (cable sheath) |
Extension tube | ABS |
Mounting clamp | PA-GF |
1) Standard conditions: TN = 20 °C and pN = 1,013.25 hPa
2) Related to adjustment reference; "fmr" = final measuring range
Subject to technical changes.